Thin-film Photovoltaics and Their Impact on a Commercial Building’s Cooling Load
By Scott Kriner, LEED AP
A white reflective roof can significantly reduce the cooling load placed on a commercial building by reducing the solar-heat gain. When a thin-film amorphous-silicon photovoltaic system is installed on such a roof, 85 percent or more of the roof surface may be covered with a product that can have a lower solar reflectance, or SR, than the roof surface. Using United Solar Ovonic’s UNI-SOLAR product as an example, the rated SR coefficient is 0.26. The lower reflectance value results in a higher solar-heat gain and creates a “penalty” in the cooling load of an otherwise cooler roof. However, the PV system is itself converting solar energy into electricity.
Using the U.S. Department of Energy Low Slope Roof Calculator and the PV Watts calculator from the National Renewable Energy Laboratory, several scenarios were used to calculate the cooling-load penalty.
Calculations performed on buildings in cities with 2006 IECC insulation levels and realistic air-conditioner coefficient of performance, or COP, values, showed the thermal cooling-energy penalty is less than 2.5 percent. This suggests that a building-integrated, thin-film PV system can generate a significant net gain of electricity, even while powering air conditioners and other energy loads in new commercial low-slope-roofed buildings, without a significant penalty to the cool-roofing performance.
Background
The Energy Independence and Security Act of 2007 authorized the formation of the Zero Net Energy Commercial Buildings Initiative. The initiative is an alliance of industrial, academic and government representatives working to transform energy performance in commercial buildings. Sponsors include DOE, ASHRAE, AIA, USGBC, The World Business Council for Sustainable Development, LBNL and the Alliance to Save Energy.
The California Public Utilities Commission recently announced a challenge to builders to construct all new commercial structures to be net-zero energy by 2030. For such a challenge to be met, significant conservation of energy and improvements to energy efficiency will be required. Renewable-energy sources, like thin-film PV systems, also will be necessary to generate on-site electricity.
In the 2008 California Building Energy Efficiency Standards, BIPV panels are exempt from the minimum prescriptive requirements for SR and thermal emittance, or TE. This is a sensible exception to the cool-roof provisions. Similarly, in the draft language of ASHRAE 189.p.1, “Standard for the Design of High Performance Green Buildings Except Low-Rise Residential Buildings,” the area of a roof covered by a PV system is exempt from the solar-reflectance-index, or SRI, criteria for the roof. These are positive developments for the use of PV systems.
Other states, such as Massachusetts, Nevada, New Jersey and New Mexico, have passed legislation or are seriously considering legislation that would require the construction of net-zero-energy buildings. The use of BIPV modules will play an integral role in any zero-energy building initiative.
Introduction
PV roof systems are a passive-renewable-energy source for converting sunlight into electricity. The generation of electricity from PV-based technology is possible through the interaction of sunlight with certain “doped” semi-conductor materials. Electrons are released from these materials resulting in a current. That direct current is then converted to alternating current with an inverter and provides electricity to power the building. The most prevalent material used in the production of photovoltaic arrays is silicon. The basic building block of PV technology is called the solar cell. (See footnote 1.)
There are two primary types of cells within silicon-based PV systems: crystalline (mono and poly) and amorphous. Crystalline PV systems currently represent 80 percent of the market. The crystalline PV wafers are typically 0.2- to 0.4-mm thick. However, once packaged in metal and glass they are approximately 0.25 to 1 inch in total thickness and require 20 kg of silicon per 1 kW of PV. An electricity conversion efficiency of 15 to 20 percent is typical. (See footnote 2.) Crystalline PV is rigid and brittle and must be housed sufficiently to maintain its single-crystal nature and avoid shattering.
Conventional crystalline-silicon PV cells are connected to form a PV module, and many modules are linked together to form a PV array. The modules consist of an assembly of silicon wafers sandwiched between two layers of glass in a metallic frame. These panels are relatively heavy but can be mounted to metal roofing with a special fastening device that does not penetrate the roof surface. A typical 4-inch silicon solar cell can produce about 1W of direct-current electricity. (See footnote 3.)
An alternative to crystalline-silicon PV modules is thin-film amorphous silicon products. The thin-film PV layers are less than 2-microns thick (0.12-inches thick with a fully encapsulated module) and are flexible and semi-transparent. These systems use 0.067 kg of silicon per kW. Amorphous silicon is deposited from silane gas, SiH4; therefore, it is not subject to the polysilicon shortage in the crystalline PV industry. Amorphous-silicon products with multi-junction cells are the typical composition of thin-film PV products. They are produced by depositing films of doped silicon-germanium alloys to a thin sheet of stainless steel and then encapsulating them with a flexible, light-transmissive top-layer. The PV material can then be laminated to the flat-pan section of a standing-seam metal roof surface, for example.
Amorphous silicon is deposited from silane gas, SiH4; therefore, it is not subject to the polysilicon shortage in the crystalline PV industry.
In general, thin-film amorphous-silicon-laminated PV modules reflect about 26 percent of incoming solar energy (i.e. SR = 0.26). Only about 6.5 percent of total solar energy that strikes the surface is converted into electricity. Because the converted energy is not absorbed but photo-electrically converted, it can be considered (in a thermal sense) part of an “effective solar reflectance” of 32.5 percent (SRe 0.325). In other words, from a thermal perspective, a thin-film PV system is similar to a cool-roof surface with SR of approximately 0.30.
In heating-dominated climates, a thin-film PV system is well suited for integration into a metal roof design. (See footnote 4.) However, in cooling-dominated climates, building owners sometimes question the thin-film PV product’s ability to generate enough power to compensate for the added air-conditioning load resulting from a higher solar-heat gain into the building. That higher solar-heat gain is caused by a relatively dark-colored PV surface with a lower SR value.
This paper looks at new commercial roofing applications for thin-film PV systems and evaluates the energy generated by the PV modules in contrast to the additional cooling load that the entire PV system thermally imparts to the roof. Research on this specific topic appears to be limited. Using available tools, calculators and data, we have determined that any penalty resulting from the UNI-SOLAR-laminated PV system is minimal.
Photovoltaic Power Generation
The actual net power balance generated by an installed PV system is affected by the overall integrity of the roof, size and efficiency of the PV system, local climate conditions (driving total solar irradiance) and wind conditions. When a thin-film PV system is installed over a very light-colored roof (high SR), there will be an added cooling load because of the darker color of the PV surface and lower SR compared to the high-reflectance roof. However, when installed over a dark-colored roof, the PV system will actually improve the thermal performance of the roof by providing a higher SR over the PV system’s covered area. When installing a thin-film PV product over a painted-metal-roof surface, the TE of both surfaces may be similar. A palette of colors, such as champagne, brown, dark bronze, green, blue, terra cotta and charcoal gray, is available as “cool” paint systems commonly used for steep-slope metal roofing. (See footnote 5.)
Thin-film amorphous-silicon PV cells offer outstanding power generation characteristics at higher temperatures. Multi-junction amorphous-silicon PV cells collect more efficiently during low-light (diffuse) conditions. Each amorphous-silicon layer in a multi-junction cell is doped to absorb red, green or blue light and layered accordingly within the cell. The nature of this thin-film PV structure means its specific angle of inclination has much less effect on the generated output than crystalline PV. As a result, amorphous silicon PV modules can generate more power per annum than crystalline PV modules of identical rated output. (See footnotes 6 and 7.)
When installed over a dark-colored roof, the PV system will actually improve the thermal performance of the roof by providing a higher SR over the PV system’s covered area.
In addition, the content of the solar spectrum can change continuously as the climate conditions change. Because amorphous-silicon thin-film PV systems produce more energy under low light levels (compared to crystalline-silicon modules) and are more efficient for greater amounts of time under variable spectrums of light, they generate more actual power per (installed) watt. They also retain their efficiency twice as well as crystalline-silicon PV modules at elevated temperatures. This means more actual power is being generated during peak sun hours when the surface temperature is above ambient.
The Energie Centrum Nederland laboratory in Europe has found that some amorphous-silicon thin-film cells can be up to 40 percent more efficient than crystalline-silicon PV products when light levels are less than ¼ suns. (See footnote 7.) Because amorphous-silicon thin-film PV products lose half as much voltage per degree of temperature increase compared to a crystalline-silicon solar cell (See footnote 8.), this means electricity is being generated for more hours per day than crystalline-silicon technologies allow.
The UNI-SOLAR thin-film PV product uses a proprietary Triple Junction color-cell technology. Each cell is composed of three semiconductor junctions, connecting different doped amorphous-silicon-germanium alloys stacked on top of each other to match the colors of light and their indexes of refraction. Each doped amorphous-silicon junction preferentially absorbs different colors of the visible light spectrum. The bottom cell absorbs red light, the middle cell absorbs green/yellow light and the top cell absorbs the blue light. The ability to wavelength-tune photovoltaic layers, essentially multiplexing, in the sun’s spectrum is one of the keys to the improved efficiencies and higher energy output for more hours of the day (even during low- or diffuse-light conditions) of amorphous-silicon thin-film PV products. In the future, micro and nanocrystalline silicon will be merged with amorphous thin films at UNI-SOLAR, promising a wider photo-conversion spectrum and even higher efficiencies.
United Solar Ovonics states that most (66 percent) of the heat that builds up at the surface of its thin-film PV modules can be dissipated through convective cooling from wind. The high TE surface (0.87) of the PV modules allows for radiative losses to the night sky which can account for another 33 percent of the heat loss. (See footnote 9.)
The best markets for thin-film PV include well-insulated buildings and new buildings that are already energy efficient. In those types of structures PV laminates would have the least thermal impact. A BIPV system would also be beneficial for reroofing projects where insulation is brought up to or in excess of code, HVAC equipment is improved and/or lighting efficiencies are increased.
Power Ratings
The actual energy yields of PV systems cannot be determined strictly on the nominal rated power of a module. The peak-power-performance labels on PV modules are based on controlled testing that is done under standard testing conditions, or STC. These conditions include holding the module temperature constant at 25 C, irradiating the surface with one type of solar spectrum and then irradiating the surface directly at 1000 W/m². However, in actual installations, PV module temperatures can be much higher (in the range of 40 to 60 C), and receive solar irradiance of 1000 W/m² less than 1 percent of the time. (See footnote 7.)
The PVUSA Test Conditions, or PTC, represent more realistic conditions. PTC are defined as 45 C (113 F) cell temperature, 1000 W/m² solar irradiance and 1 m/s wind speed. This test was developed in an attempt to simulate what happens in a real-world outdoor installation. Usually, the PTC rating for a PV panel is between 70 and 85 percent of the STC rating. The reason the PV panels produce less power under these conditions has to do with the material properties of the PV modules. As stated previously, amorphous-silicon PV has about half the power loss per degree of temperature increase compared to crystalline-silicon PV technology. On a hot, sunny day with a 40-degree-above ambient surface temperature, this translates into more power for the amorphous thin-film customer.
DOE Low Slope Roof Calculator
The DOE Low Slope Cool Roof Calculator was used to evaluate the impact of the “darker” thin-film amorphous-silicon PV systems on the heat gain into a building. The calculator allows one to compare the cooling energy and cooling loads of a building with a roof of interest to that of a building with a black roof as the reference in any location. (See footnote 10.)
To determine a worst-case condition, or the greatest anticipated cooling load encountered, we chose Phoenix as the location because of the high solar-radiance levels. We also used an R-5 level of roof insulation, recognizing that this level is well below code for the required R-value. Another assumption for the worst-case calculation was that the air-conditioner unit has a COP of 2.0. Again, this is lower than what is commonly installed as new air-conditioning units. (See footnotes 12 and 13.)
Starting with a low-slope white roof as the ideal case for a cool roof (i.e. lowest cooling load to the building) compared to a black roof, we input the initial SR of 0.70 and initial TE of 0.90 into the calculations. We also calculated the cooling load for a roof that is covered 100 percent with a thin-film PV, using an SRe of 0.30 and TE of 0.90.
The results from the DOE calculator compare both types of roofs to a black roof. The values below indicate the effect of the different SR values on the cooling load.
| Black reference | Thin-film PV* | White roof** |
| 35,801 | 27,477 | 13,919 |
* Assuming 100 percent coverage, total solar reflectance 0.30, TE 0.90
** TSR 0.70, TE 0.90
In reality, a roof with laminated-thin-film PV modules is never fully covered. For example, the size of an individual UNI-SOLAR panel is 18-feet long by 15½-inches wide, each rated at 136W. If we use a 100,000-square-foot roof, measuring 80 by 1,250 feet, it would allow for 937 rows of PV panels laminated within the 16-inch width of a standing-seam metal roof pan. Four panels would run from the eave to ridge and down again to the other eave (72 feet in total length). With that layout, a total of 3,748 panels would be installed, each 23¼ square foot in area and generating 510 kW (3,748 panels x 136W per panel). That would yield a total PV surface area of 87,141 square feet compared to the total roof surface area of 100,000 square feet, or an 87 percent coverage factor.
The calculation must be modified to take into account the thin-film PV cooling load applies to only 87 percent of the roof surface, and the cool white roof’s effect applies to the remaining 13 percent of the surface. That calculation is shown below:
| Thin-film PV load x 87% 23,905 BTU/square foot/year |
| White load x 13% +1,809 BTU/square foot/year |
| Effective cooling load 25,714 BTU/square foot/year |
To determine the extra cooling load the thin-film PV laminated roof creates, as compared to a white cool roof, we must subtract the effective cooling load of the roof from the fully covered white roof.
| 25,714 -13,919 = 11,795 BTU/square foot/year |
To convert this value into energy expressed as kWh/ft²/year we must use a conversion factor. The traditional conversion factor between these two units would be 3,413 BTU per kWh. However in the case of air-conditioning energy, that conversion applies only when the COP is 1.0. For the worst-case scenario, we are assuming an air-conditioning-unit COP of 2.0, which changes the conversion factor to 6,826 BTU/kWh.
- Converted to kWh/square foot/year = 1.73
This then becomes our cooling-load penalty resulting from the thin-film PV laminated product on the white roof.
Because the energy yield from a PV system cannot be determined on the basis of labeled nominal power of the module, another way to evaluate the energy was necessary. Under outdoor conditions the irradiance and ambient temperatures are constantly changing. (See footnote 7.) At these non-standard conditions, the characteristics of the modules are often unknown.
The PV Watts calculator developed by NREL allows one to calculate the energy produced by a PV system in any location on a monthly basis. The input parameters include the DC rating, DC to AC derate factor, type of array, array tilt and array azimuth. Using Version 1 of this calculator allowed us to determine the monthly and annual energy generated by a thin-film PV system in select cities. (See footnote 11.)
To calculate the actual energy generated by the PV module, we assume a 100,000-square-foot roof area. With the assumptions and values used for our worst-case scenario, the Version 1 calculator yielded the following energy for a PV installed on this type of building in Phoenix:
| Assumptions: |
DC rating 510 kW** DC to AC de-rate factor 0.770 AC rating 3.85 kW Array tilt 10° (2:12 low slope) Array azimuth 180° (facing south) |
| 775,105 kWh/year |
*Based on calculation from www.pvwatts.org
**DC rating of 5.1 kW/1,000 square feet for UNI-SOLAR
Now the calculated annual energy generated from a PV unit in Phoenix is known. To compare this energy generated against the added cooling energy resulting from the PV surface itself, we use the 100,000-square-foot roof surface area assumption and apply the extra cooling load of 1.73 kWh/square foot/year to yield 173,000 kWh/year. The ratio of the extra cooling load to the energy generated gives us the cool-roof penalty expressed in a percentage of the total energy generated.
|
Extra cooling load from UNI-SOLAR vs. White 100,000 x 1.73 = |
173,000 kWh/year |
| PV energy generated | 775,105 kWh/year |
| Ratio: 173,000 / 775,105 | 22% of PV energy |
*100,000-square-foot roof
From this example in Phoenix, we used specific conditions that were representative of an older building (a reroofing project where PV is installed) with insulation levels below the 2006 IECC levels and inefficient air-conditioning units. The calculations suggest that, at most, about 20 percent of the energy generated by the thin-film PV modules would be required to compensate for the added cooling load from the penalty of the dark surface of the PV product.
To look at a more practical comparison, other calculations were performed using different cities, levels of insulation based on the 2006 IECC and an average commercial air-conditioner COP of 3.0 as indicated in the DOE Buildings Energy Data Book of 2007. (See footnotes 12 and 13.) For the white roof in these more practical calculations, we used an aged SR of 0.55 and an aged TE of 0.75 to be consistent with the proposed 2008 California Building Energy Efficiency Standards in Title 24, Part 6.
New construction would comply with the 2006 IECC code with higher R-values of roof insulation entirely above deck and higher efficiency of new air-conditioning units. Because the radiant properties of a roof can change over time, a more realistic approach to calculating the long-term cooling loads would be to use aged values of SR and TE.
By increasing insulation and the COP, as well as using aged values of the radiative properties of the cool roof, a significant reduction in the penalty was achieved. In all of the practical cases, the calculators suggest that less than 2.5 percent of the energy generated by the thin-film PV modules were needed to compensate for the added cooling load. Thus, the thin-film PV system can generate more than enough energy to offset any additional cooling load caused by the darker-colored PV product.
A summary of those calculations, using a 100,000-square-foot roof system, for practical cases is shown below:
| City |
ASHRAE Climate Zone |
2006 IECC Above-deck Insulation | Extra Annual Cooling Load from Thin-film PV (kWh) | Annual PV Energy Generated (kWh) | Percent of PV Energy Used to Compensate for Cooling-load Penalty |
| Miami | 1 | R-15 | 16,600 | 664,716 | 2.5 |
| Houston | 2 | R-15 | 13,100 | 603,038 | 2.2 |
| Phoenix | 2 | R-15 | 18,000 | 775,105 | 2.3 |
| Charleston, S.C. | 3 | R-15 | 11,500 | 644,200 | 1.8 |
| Los Angeles | 3 | R-15 | 4,300 | 709,351 | 0.6 |
| San Francisco | 3 | R-15 | 700 | 693,585 | 0.1 |
| St. Louis | 4 | R-15 | 9,000 | 604,301 | 1.5 |
| Chicago | 5 | R-20 | 3,800 | 564,717 | 0.7 |
| Minneapolis | 6 | R-20 | 3,400 | 587,153 | 0.6 |
The level of roof insulation has a significant impact on the cooling-load penalty. Using aged SR and TE values for a white roof in the DOE Low Slope Roof Calculator, we can compare an R-5 scenario against a code-compliant R-15 scenario in Phoenix, for example (see below). The calculations are made using a 100,000-square-foot roof as the example. As expected, the roof systems with lower insulation values result in higher cooling loads. The effect of increasing the insulation from R-5 to R-15 in that location is a 65 percent reduction in the extra cooling load caused by the thin-film PV system (52,600 kWh vs. 18,000 kWh).
| Insulation | Effective Annual Roof Cooling Load (BTU) | Extra Cooling Load from Thin-film PV (kWh) | Annual AC Energy Generated by PV (kWh) | Percent of PV Energy to Compensate for Cooling-load Penalty |
| 5 | 2,667,300,000 | 52,600 | 775,105 | 6.8 |
| 15 | 918,300,000 | 18,000 | 775,105 | 2.3 |
Similarly, the SR and TE of the reference roof surface have an impact on the cooling-load penalty. Using a 100,000-square-foot roof in Phoenix again, we can compare the results from a cool roof where the aged properties are used in the calculation versus results from a cool roof where the initial values are used. The DOE Low Slope Roof Calculator was used for this comparison, using R-15 insulation levels for both cases. A white roof was assumed as the reference with an initial TSR of 0.70 and initial TE of 0.90. In comparison, a white roof with an aged total solar reflectance of 0.55 and aged TE of 0.75 was used as a more practical scenario. The impact on the extra cooling load was not as dramatic as that seen with different insulation levels. The calculations show that using the lower TSR/TE values for an aged surface resulted in a 55 percent reduction in the extra cooling load caused by the thin-film PV system (40,300 kWh vs. 18,000 kWh).
| TSR | TE | Effective Annual Roof Cooling Load (BTU) | Extra Annual Cooling Load from Thin-film PV (kWh) | Annual AC Energy Generated by PV (kWh) | Percent of PV Energy to Compensate for Cooling-load Penalty |
| 0.55 | 0.75 | 918,300,00 | 18,000 | 775,105 | 2.3 |
| 0.7 | 0.9 | 884,100,000 | 40,300 | 775,105 | 5.2 |
It is important to note that the calculations that were performed in this study focused only on the annual cooling loads determined by the DOE Low Slope Roof Calculator. In colder climates, the darker surface of the thin-film laminates may be beneficial in lowering the overall annual combined cooling/heating energy use.
Conclusions and Comments
- Variables, such as insulation, wind speed and direction, and solar irradiance, can complicate the evaluation of a cooling-load penalty.
- A thin-film amorphous-silicon PV system installed on a new low-slope cool metal roof causes less than a 2.5 percent penalty to the electricity generated by the PV system, despite causing a slightly higher cooling load.
- A worst case scenario with low insulation, a poor air-conditioning COP and high solar radiance causes a 22 percent cooling load penalty. An example of this would be a case where reroofing or adding PV to an existing older building takes place. In that case, insulation levels would be relatively lower and air-conditioning equipment efficiencies would be much lower than that of new equipment.
- The level of roof insulation has a significant impact on the effective roof cooling load and cooling-load penalty from the thin-film PV system.
- Calculations suggest that for new construction the energy generated by thin-film PV modules far exceeds the energy required for extra cooling that is caused by higher solar-heat gain from the darker PV surface.
- The SR/TE values of today’s thin-film PV modules are similar to other steep-slope cool metal roof surfaces as defined by the Energy Star roof products program. As thin-film PV modules’ photoelectric-conversion efficiencies rise so will the effective SR, improving the thermal footprint (cooling-load penalty).
- Installing thin-film PV modules on a cool metal roof is prudent to capitalize on those areas of the roof that are not covered with PV modules.
Scott Kriner is president of Green Metal Consulting, Macungie, Pa., and a member of Eco-Logic's advisory board.
Recommended Further Study
- Verification comparison via FLIR camera and quantitative heat study with modeling of UNI-SOLAR and competitor panels on various rooftops under various light and temperature conditions.
- Refinement of model using NREL’s Solar Advisor Model for equipment specific I-V and Power-Efficiency curves designed into PV array scenario with higher precision, location specific, climate modeling.
Footnotes
(1) Melody, I., “Photovoltaics: A Question and Answer Primer,” Florida Solar Energy Center, Publication Number FSEC-EN-11-83, February 1985.
(2) Parker, T. and Moine, G., “Amorphous Silicon and Crystalline Modules: Similarities and Differences,” Powerpoint information from UNI-
SOLAR.
(3) Melody, I., “Photovoltaics: A Question and Answer Primer,” Florida Solar Energy Center, Publication Number FSEC-EN-11-83, February 1985.
(4) Miller, W.A., Brown, E., Jo Livezey, R., Dual, “2004: Building Integrated Photovoltaics for Low-Slope Commercial Roofs,” Proceedings of 2004 Solar Conference, Portland, Ore., July 2004.
(5) Miller, W.A., Desjarlais, A.O., Kriner, S., “The Thermal Performance of Painted and Unpainted Standing Seam Metal Roof Systems Exposed to Two Years of Weathering,” Presented at Thermal Performance of the Exterior Envelopes of Whole Buildings VIII, Clearwater, Fla., December 2001.
(6) Mitsubishi Heavy Industries Ltd., “Photovoltaic Power Generation Utilizing Renewable Energy Available in Unlimited Supply.
(7) Eikelboom, J.A. and Jansen, M.J., “Characterisation of PV Modules of New Generations,” ECN-C-00-067, June 2000.
(8) Van Cleef, M.,Lippens, P., Call, J., “Superior Energy Yields of UNI-SOLAR Triple Junction Thin Film Silicon Solar Cells Compared to Crystalline Silicon Solar Cells under Real Outdoor Conditions in Western Europe,” Presented at 17th European Photovoltaic Solar Energy Conference and Exhibition, October 2001, Munich, Germany.
(9) Ellison, T., “Building Integrated Photovoltaics (BIPV) And The ‘Cool Roof’,” Presented at Solar 2004, Portland, Ore., July 2004.
(10) U.S. Department of Energy, Cool Roof Calculator, www.ornl.gov/sci/roofs+walls/facts/CoolCalcEnergy.htm.
(11) National Renewable Energy Laboratory, PV Watts Calculator, www.pvwatts.org.
(12) U.S. Department of Energy, Office of Public Affairs, Press Release: “Stronger Manufacturers’ Energy Efficiency Standards for Residential Air Conditioners Go Into Effect Today,” www.energy.gov/print/3097.htm, January 2006.
(13) U.S. Department of Energy, Buildings Energy Data Book, September 2007.










Comments:
There are currently no comments for this page. Be the first to leave one!
Post A Comment: